Building

Amnet Colo is located in a private gated 10,000 square foot single story building within a secure fenced in area. Access through automatic gates is provided only to clients holding a valid card access ID.

Space Specification

Colocation area is located in a secure raised floor data center environment with underfloor cooling and overhead cable trays. We offer cabinets, cages and custom high security private suite configurations.

Cabinets

  • Dimensions - 30" W x 36" D x 84" H
  • Rails - 4 post 19" or 23" configuration
  • Full, half and one third cabinets available
  • All cabinets are locked
  • Multiple "ganged" cabinets available

Cages

  • Dimensions 8' x 8' and 10' x 10'
  • Secure locked entrance doors
  • Custom power configuration available

Private Rooms

  • Custom engineered upon request

Environmental / HVAC

All environmental control provided by Liebert System 3 Environmental Control Units. These units are specifically designed for mission critical data center applications and have been engineered to provide 150 BTU/h per square ft.

  • Temperature is maintained at 72 degrees (+/- 2 degrees)
  • Humidity is maintained at 45% (+/- 5%) using infra-red humidifiers
  • All ECU's are fully backed up by diesel generator
  • N+1 redundancy

Electrical Service

Oversized electrical service providing 100 watts per square foot guarantees future growth will never disrupt our clients.

  • 2000 amps @480 volt
  • Underground feed with transformer inside gated area of facility
  • All state-of the-art Square D switchgear, transformers and distribution panels
  • Conduits installed under road are encased in concrete with a steel plate on top to eliminate the possibility of road construction interfering with any services to our building.
  • 120/208 volt and -48VDC also available

Ground Buss System

A professionally engineered ground buss system is in place.

  • Master Ground Plate terminates all ground wires back to a common point
  • Ground buss distribution cable runs from the ground plate to each cabinet via the overhead cable tray.
  • There is an "H-Tap" connection from the overhead ground distribution cable which delivers a ground to each cabinet. This insures proper cabinet frame to ground potential.

Generator

Backup power for all environmental control units, AC and DC to the colocation area is provided by an ONAN 375 KW diesel generator

  • 1000 gallon diesel storage tank provides 48 hours of full load run time
  • Priority refueling contracts in place
  • Automatic transfer switch brings generators on-line in less than 12 seconds following a commercial power outage.
UPS System

UPS System backs up and conditions power for all AC power in the colocation area. This is provided by a Liebert Series 3 UPS. This system is one of the most reliable on the market today. It has an estimated run time of 30 years.

  • Backup generator providers power to the UPS system
  • 15 min. battery time (generator takes 12 seconds to transfer in a commercial power outage)
  • UPS output connects to a PDU (Power Conditioning & Distribution unit)
  • PDU creates separately derived service and neutral conductor thus providing clean A/C power to all outlets.

DC Power

All -48 Volt DC power provided by a state-of-the-art Liebert Helios DC power plant

  • -48VDC power custom configured for each client
  • A/B feeds available
  • 2 hour battery backup (generator takes only 12 seconds to take over in a commercial power failure)
  • Generator backs up all DC power

Fire Suppression Systems

The colocation area, "Meet Me" room and electrical service room are all protected by a Kiddie FM200 non-toxic gas suppression system. This system will extinguish a fire without the use of water.

Security

  • Access to colocation area requires clearing 4 points of authentication.
    1. Access card verification at automatic gate entry to parking lot
    2. Access card verification at door to front lobby
    3. Access card & hand geometry scan at entrance to Colo hallway
    4. Access card & pin code to enter into the Colo Data Center

  • 24/7 access to authorized individuals
  • Digitally recorded color CCTV surveillance
  • All equipment in Colo room perimeter and roof of building are constantly monitored
  • Security policies are in place and are strictly enforced
  • All access to facility is logged and stored in a database along with a digital picture of each authorized individual

Common Work Area

A common work area is provided for our clients. This area consists of a desk and a phone outside of the colocation room.

  • Work area and phone with a direct phone number allowing our clients to page their colleagues and receive a direct call back.
  • All long distance calls are the client's responsibility.

Carrier Access Providers

We have pre-installed conduits inside and outside the facility to assure rapid connection to any new carrier. We encourage new carriers to "build-out" to our facilities so we can provide diverse network interconnectivity to our clients.

  • Separate "Meet Me" room designed into building for secure interconnectivity to multiple carriers
  • All carrier fiber is protected in conduit from the street to our "Meet Me" room
  • Fiber service conduits installed under road are encased in concrete with a steel plate on top
  • FM 200 waterless fire protection is installed in the "Meet Me" room
  • Anyone requiring access to the "Meet Me" room must be escorted by an authorized Amnet Colo employee

On-Net access available from the following carriers:

  


Zero-mile access available from the following carriers:


   

      

 

  About Us | Facilities | Solutions | Partners | Home
  Contact Us | Site Map | Request A Quote
 
Toll Free: 866-USA-COLO | Headquarters: 203-355-2500
Email: info@amnetcolo.com | URL: www.amnetcolo.com
 
© Copyright 2001, Amnet Colocation Centers. All rights reserved.